Leave Your Message

Banatton Understanding Online Three-Phase and Pure Sine Wave UPS Systems-1

Brand: Banatton

Place of origin: China

Type: online UPS

Model Number: BNT9300-M 20~300KVA

Phase: Three Phase

Waveform: Pure sine wave

Transfer time: 0ms

Power factor: 0.9

Capacity: 20KVA-300KVA

Protection: short-circuit, over voltages, reverse connection protection

OEM/ODM: Yes

Supply Ability: 5000 Piece/Pieces per Month

Packaging: Carton or wooden box package or as you requested

    product detail

    Description

     

    Brand: Banatton

    Place of origin: China

    Type: online UPS

    Model Number: BNT9300-M 20~300KVA

    Phase: Three Phase

    Waveform: Pure sine wave

    Transfer time: 0ms

    Power factor: 0.9

    Capacity: 20KVA-300KVA

    Protection: short-circuit, over voltages, reverse connection protection

    OEM/ODM: Yes

    Supply Ability: 5000 Piece/Pieces per Month

    Packaging: Carton or wooden box package or as you requested

     

    Features

    Title: The Ultimate Guide to Choosing the Right Uninterruptible Power Supply (UPS) for Your Business In today’s fast-paced world, businesses rely heavily on technology to operate efficiently. From small startups to large enterprises, uninterruptible power supply (UPS) systems play a vital role in ensuring that critical equipment and systems remain operational during power outages. With a wide variety of UPS options available in the market, choosing the right UPS for your business can be a daunting task. In this guide, we’ll explore the key factors to consider when choosing a UPS, focusing on UPS 30KVA and 60KVA UPS systems. 1. Understanding the Basics of Uninterruptible Power Supply (UPS) An uninterruptible power supply, commonly known as a UPS, is a backup power system that provides emergency power to the load when the input power fails. UPS systems are designed to protect equipment from power disturbances such as power outages, voltage fluctuations, and frequency changes. They come in a variety of sizes and capacities, with 30KVA and 60KVA UPS being popular choices for medium and large businesses. 2. Factors to Consider When Choosing a UPS When choosing a UPS for your business, there are several factors to consider. These include the power capacity, efficiency, scalability, and reliability of the UPS system. In addition, it is important to consider the specific requirements of your business, such as the criticality of the equipment being protected and the duration of backup power required during a power outage. 3. 30KVA UPS vs. 60KVA UPS: Making the Right Choice Both 30KVA and 60KVA UPS systems are designed to provide backup power to medium and large businesses. The 30KVA UPS is suitable for businesses with medium power needs, balancing capacity and cost-effectiveness. On the other hand, the 60KVA UPS is ideal for businesses with higher power requirements and requiring greater scalability. 4. The Importance of Google SEO in Finding the Right UPS In today's digital age, businesses often turn to search engines such as Google to find information and products. Implementing an effective SEO strategy can help UPS manufacturers and suppliers reach their target audience and drive organic traffic to their websites. By incorporating relevant keywords such as "UPS 30KVA," "Uninterruptible Power Supply," and "60KVA UPS" in their content, businesses can increase visibility and attract potential customers. 5. Conclusion Choosing the right UPS for your business is a critical decision that requires careful consideration of a variety of factors. Whether you choose a 30KVA UPS or a 60KVA UPS, it is vital to evaluate your power needs, budget, and long-term business goals. By understanding the basics of UPS systems and leveraging SEO strategies to find the right supplier, you can ensure that your business stays powered and running even during unexpected power outages. In summary, choosing an uninterruptible power supply is a crucial decision for any business. By understanding the key factors and leveraging SEO strategies, businesses can make an informed decision and find the right UPS solution for their specific needs. Whether it's a 30KVA UPS or a 60KVA UPS, the goal remains the same: to keep the lights on and running smoothly no matter what.

     

    Modular UPS (8).jpg

     

    Modular UPS (9).jpg

     

    Little Hint

     

    1. In the warranty period the machine has a problem, please contact the sales staff, we will be responsible for customer service.

    2. Exceed the warranty period, improper operation and man-made damage, we will still give help and support, we will provide spare parts at a cost price.

    3. According to the customer's needs, we can provide unconventional, but the cost may be slightly higher than the traditional machine.

     

    Applications

     

    Modular UPS (10).jpg

     

    Data processing center, The host system, Computer servers, Medical, Traffic, Electricity, IT, Industrial and other industries.

     

    Factory Production Line

     

    Modular UPS (11).jpg

     

    Modular UPS (12).jpg

     

    Modular UPS (13).jpg

     

    Packaging

     

    Modular UPS (14).jpg

    Technical Parameters

    MODEL

    BNT990-M

    BNT9150/180-M

    BNT9300-M

    Rated Capacity

    Cabinet Capacity

    20-90kVA / 20-90kW

    25-150kVA / 25-150kW  30-180kVA / 30-180kW

    30-300kVA / 30-300kW

    One Ppwer Module Capacity

    20kVA /20kW, 25kVA /25kW,30kVA /30kW

    MAX. Power Module NO.

    3

    5/6

    10

    INPUT


    Main Input

    Nominal Voltage(Vac)

    380/400/415

    Voltage Range(Vac)

    138~485Vac;305~485Vac load,138~305Vac load

    Phase

    3-phase in / 3-phase out

    Nominal Frequency(Hz)

    40-70

    Power Factor

    ≥0.99

    Harmonic Distortion (THDi)

    ≤3% (100% load)

    Bypass Input

    Nominal Voltage(Vac)

    380/400/415

    Voltage Range(Vac)

    220 Vac:25%(+10%,+15%,+20%)

    230 Vac:20%(+10%,+15%)

    240 Vac:15%(+10%);-45%(-10%,-20%,-30%)

    Phase

    3-phase in / 3-phase out

    Power Walking In

    YES

    Bypass Back Irrigation

    YES

    Generator Access

    YES

    OUTPUT


    Voltage(Vac)

    380/400/415±1%

    Power factor

    1

    Frequency(Hz)

    AC Mode

    ±1%/±2%/±4%/±5%/±10%

    Battery Mode

    (50/60±0.1%)Hz

    Waveform

    Pure Sinewave

    Admissible Crest Factor

    3:01

    Harmonic Distortion(THDV)

    ≤2% (100%Linear Load);≤3% (100%Non-linear Load)

    Transfer Time(ms)

    0

    Efficiency(%)

    95.50%

    Overload Capability

    1 hour for 110%, 10 mins for 125%,1 min for 150%, 200ms for >150%

    BATTERY


    Maximum Charging Current(A)

    18

    Nominal Voltage

    ±180V/±192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc

    (30/32/34/36/38/40/42/44/46/48/50 pcs)

    ENVIRONMENT


    Operating Temperature

    0℃~40℃

    Storage Temperature

    -25℃~55℃

    Relative Humidity

    0~95%

    Altitude

    < 1500m

    Noise Level(dB)

    <58dB

    <61dB

    <68dB

    PHYSICAL


    Dimension (D x W x H) mm

    UPS Cabinet

    600×850×1350

    600×850×1350          600×850×1550

    600×850×2000

    Module

    440×620×86

    Net Weight(kg)

    UPS Cabinet

    140

    155/170

    290

    Module

    21